H07ZZ-F Cable

- Eland Product Group:
- A6G and A5G
- Application:
- For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment. Examples of use include supplying mobile power units, UPS installations, stage lighting and audio visual equipment. This cable will withstand medium mechanical stresses and is suitable for both installation indoors and outdoors.
- Standards:
CENELEC HD22-13
NFC 032-131
IEC 60332-3- Conductor:
- Class 5 flexible plain copper to BS EN 60228:2005 (previously BS6360)
- Insulation:
- Halogen free elastomer
- Sheath:
- Halogen free elastomer
- Sheath Colour:
- Black
- Voltage Rating:
- 450/750V
- Temperature Rating:
- Conductor operating temperature -25°C to +60°C (85°C max)
- Minimum Bending Radius:
Up to 25mm²: 4 x overall diameter
Above 25mm²: 6 x overall diameter- Core Identification:
2 Cores: Blue, Brown
3 Cores: Green/Yellow, Blue, Brown
4 Cores: Green/Yellow, Brown, Black, Grey
5 Cores: Green/Yellow, Blue, Brown, Black, Grey
6 Cores and above: Black with White numerals, Green/Yellow
Specifications Data
Download detailed H07ZZ-F Cable specifications as a PDF file (290kb)
| No. of Cores x Nominal Cross Sectional Area# x mm² | Nominal Overall Diametermm | Nominal Weightkg/Km | FCGA2 GlandBrass | FCGA2PL GlandPlastic |
|---|---|---|---|---|
| 1 x 1.5 | 7.1 | 63.0 | - | - |
| 1 x 2.5 | 7.9 | 76.0 | - | - |
| 1 x 4.0 | 9.0 | 107.0 | - | 20 |
| 1 x 6.0 | 9.8 | 140.0 | 20S | 20 |
| 1 x 10.0 | 11.9 | 213.0 | 20 | 20 |
| 1 x 16.0 | 13.4 | 291.0 | 20 | 25 |
| 1 x 25.0 | 15.8 | 415.0 | 25 | 25 |
| 1 x 35.0 | 17.9 | 539.0 | 25 | 25 |
| 1 x 50.0 | 20.6 | 740.0 | 32 | 32 |
| 1 x 70.0 | 23.3 | 989.0 | 32 | 32 |
| 1 x 95.0 | 26.0 | 1290.0 | 32 | 40 |
| 1 x 120.0 | 28.6 | 1592.0 | 40 | 40 |
| 1 x 150.0 | 31.5 | 1957.0 | 40 | 40 |
| 1 x 185.0 | 34.4 | 2350.0 | 50S | 50 |
| 1 x 240.0 | 38.3 | 3099.0 | 50 | 63 |
| 1 x 300.0 | 41.9 | 3687.0 | 50 | - |
| 1 x 400.0 | 46.8 | 4850.0 | 63S | - |
| 1 x 500.0 | 52.0 | 5998.0 | 63 | - |
| 2 x 1.0 | 10.0 | 112.0 | - | - |
| 2 x 1.5 | 11.0 | 135.0 | 20S | 20 |
| 2 x 2.5 | 13.1 | 190.0 | 20 | 25 |
| 2 x 4.0 | 15.1 | 255.0 | - | - |
| 2 x 6.0 | 16.8 | 335.0 | - | - |
| 2 x 10.0 | 22.6 | 590.0 | - | - |
| 2 x 16.0 | 25.7 | 821.0 | - | - |
| 2 x 25.0 | 30.7 | 1172.0 | - | - |
| 3 x 1.0 | 10.7 | 125.0 | - | - |
| 3 x 1.5 | 11.9 | 129.0 | 20 | 20 |
| 3 x 2.5 | 14.0 | 250.0 | 25 | 25 |
| 3 x 4.0 | 16.2 | 330.0 | - | - |
| 3 x 6.0 | 18.0 | 440.0 | - | - |
| 3 x 10.0 | 24.2 | 800.0 | - | - |
| 3 x 16.0 | 27.6 | 1150.0 | - | - |
| 3 x 25.0 | 33.0 | 1680.0 | - | - |
| 3 x 35.0 | 52.0 | 2170.0 | - | - |
| 4 x 1.0 | 12.5 | 170.0 | - | - |
| 4 x 1.5 | 13.1 | 196.0 | 20 | 25 |
| 4 x 2.5 | 15.5 | 275.0 | 25 | 25 |
| 4 x 4.0 | 17.9 | 388.0 | 25 | 25 |
| 4 x 6.0 | 20.0 | 515.0 | 32 | 32 |
| 4 x 10.0 | 26.5 | 882.0 | 40 | 40 |
| 4 x 16.0 | 30.1 | 1234.0 | 40 | 40 |
| 4 x 25.0 | 36.6 | 1811.0 | 50S | 50 |
| 4 x 35.0 | 41.1 | 2365.0 | 50 | 63 |
| 4 x 50.0 | 47.5 | 3212.0 | 63S | - |
| 4 x 70.0 | 54.5 | 4320.0 | - | - |
| 4 x 95.0 | 60.5 | 5572.0 | - | - |
| 4 x 120.0 | 65.5 | 6930.0 | - | - |
| 4 x 150.0 | 74.0 | 8419.0 | - | - |
| 4 x 185.0 | 79.5 | 10165.0 | - | - |
| 4 x 240.0 | 90.0 | 13420.0 | - | - |
| 5 x 1.0 | 13.5 | 205.0 | - | - |
| 5 x 1.5 | 14.4 | 242.0 | 25 | 25 |
| 5 x 2.5 | 17.0 | 341.0 | 25 | 25 |
| 5 x 4.0 | 19.9 | 495.0 | 32 | 32 |
| 5 x 6.0 | 22.2 | 642.0 | 32 | 32 |
| 5 x 10.0 | 29.1 | 1090.0 | 40 | 40 |
| 5 x 16.0 | 33.3 | 1534.0 | 50S | 50 |
| 5 x 25.0 | 40.4 | 2291.0 | 50 | 63 |
| 5 x 50.0 | 53.0 | 3950.0 | 63S | - |
| 7 x 1.5 | 18.5 | 355.0 | 25 | 32 |
| 12 x 1.5 | 22.4 | 660.0 | 32 | 32 |
| 19 x 1.5 | 27.5 | 788.0 | 40 | 40 |
| 21 x 1.5 | 31.5 | 1077.0 | 40 | 40 |
| 37 x 1.5 | 36.5 | 1358.0 | 50S | 50 |